Figure 1 shows the current step in the evaluation
methodology…
Figure 1 Showing the current step (step 5: accounting for
round trip efficiency) in the methodology for evaluating a facility level
energy storage deployment.
Because the round trip efficiencies of each storage
device is less than 100%, more energy will be consumed during the charge phase
than will be delivered during discharge. This will increase the overall energy
consumed in a day. This increase in overall energy must be taken into account
when determining the cost benefit of each energy storage system. The additional
energy required, per day, is found using the following equation:
For
the LightSail RAES V1 a round trip efficiency of 70% was used while a
round trip efficiency of 85% was used for the VRB-ESS®. The additional energy
costs resulting from the round-trip efficiency of the energy storage system
were found using the following equation:
These additional, round trip efficiency related
energy costs were subtracted from the demand charge management savings for each
energy storage device to provide a more accurate estimate of overall savings.
The extent to which the round trip efficiency reduces the demand charge savings
depends heavily on the facility’s energy billing scheme. If peak energy costs
are significantly greater than the off-peak energy costs (which is common for
larger facilities) it may be possible that the demand charge savings reduction
may be eliminated or reversed by the fact that inexpensive energy is being used
to charge the device. Discharging the device during peak periods could, in this
case, allow the device to also be profitably deployed in an arbitrage
or Time
Of Use (TOU) energy cost management application. The facility that housed
the software company had a relatively unique billing scheme, for a facility of
its size, because the same energy rate was paid during peak and off-peak
periods. In that example the increased energy to overcome the round trip
efficiency directly reduced the demand charge management savings.
Figure 2 showing the Load profile on peak usage day
at the facility. The dashed line represents the peak that would be realized if
the energy storage device were operated at full power.
Many modern energy storage devices
require a charging time that is equal to or only slightly greater than the
discharge interval. There are some devices which can actually charge faster
than they discharge. In Figure 2, the time interval for the area below the
dashed line and above the load curve represents the charging interval for the
energy storage device. By visual inspection it is seen that the charging
interval area is more than twice the discharge area. If the charging interval
area were not clearly at least twice the discharge area it would be important
to pay more attention to the duration of the charging interval. It would not be
an effective energy storage device deployment if charge interval were so large
that it impacted the devices ability to reduce the peak power.
No comments:
Post a Comment